Welcome to Canconnect. We Simplify Your Field bus Experience with our web store

CAN-CR200

$511.50

CAN-CR200

Modular ISO 11898-2 CAN repeater
with backbone bus

The CAN-CR200 is used for the galvanic isolation of two segments of a CAN network and for creating star or tree topologies. Several CAN-CR200 can be connected to a CAN-hub via the integrated backbone bus. One special feature of the Repeater is the automatic recognition and separation of a defective segment from the rest of the network so that the remaining network can continue working. After elimination of the defect, the segment is switched into the network again.

The galvanic isolation isolates the CAN segments from each other as well as from the power supply.

-
+

Description

CAN-CR200

Modular ISO 11898-2 CAN repeater

with backbone bus

The CAN-CR200 is used for the galvanic isolation of two segments of a CAN network and for creating star or tree topologies. Several CAN-CR200 can be connected to a CAN-hub via the integrated backbone bus. One special feature of the Repeater is?the automatic recognition and separation of?a defective segment from the rest of the network so that the remaining network can continue working. After elimination of the defect, the segment is switched into the network again.

The?galvanic isolation isolates the CAN segments from?each other as well as from the power supply.

Features and Benefits

DIN-Rail backbone bus to line up and connect the devices easily

Cost savings due to simple wiring

Increased system reliability

Almost no influence on real-time behaviour

Technical specifications

Display : Transmit and defective segment (three duo LEDs), Power (one LED)

CAN bus interface : ISO 11898-2 with CAN choke. Two Sub-D9 connectors and one backbone bus. CAN termination resistors are integrated (switchable).

Baudrate : Up to 888 kbps

Delay : 200 ns (corresponds ~40 m (~120ft.) bus length)

Power supply : 9-32 V DC, 1.5 W typ., through terminals (Not included with the product, customer must make provision for this power supply)

Galvanic isolation : 1 kV, 1 sec.; CAN 1, CAN 2 and backbone bus are galvanic isolated against each other.

Certification : CE, FCC

Temperature range : ?-20 ?C … +70 ?C

Housing, size : Plastic enclosure, 22.5 x 100 x 115 mm

Requires T-Bus connector- item number: 1.04.0073.00000 for creating star/ tree topology in CAN Bus (Not included with the product).